Sulphur dioxide (SO2) gas detector
Fixed sulphur dioxide (SO2) detectors for fruit preservation, winemaking and processes: electrochemical cell, 0-50 or 0-2,000 ppm, 4-20 mA outputs, Modbus and relays depending on the model. Choose the model below to see its specifications and options.
Fixed sulphur dioxide (SO2) detectors for fruit preservation, winemaking and processes: electrochemical cell, 0-50 or 0-2,000 ppm, 4-20 mA outputs, Modbus and relays depending on the model.
Why detect SO2?
Sulphur dioxide is used to preserve some fruit, such as table grapes, and in winemaking; it also appears in industrial processes. Toxic and irritant, heavier than air, it must be monitored in treatment rooms and in rooms where it is stored or injected.
The sensor
Electrochemical cell, 0-50 ppm (personal safety) or 0-2,000 ppm (process) ranges, operation from −30 to +50 °C, lifetime over 2 years, checked every 6 months.
Where to install an SO2 detector?
Low, near the sources and injection points, with a remote alarm at the entrance of treatment rooms.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2638-SO2 | electrochemical | 0-50 or 0-2,000 ppm | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2639-SO2 | electrochemical | 0-50 or 0-2,000 ppm | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2608-SO2 | electrochemical | 0-50 or 0-2,000 ppm | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-SO2 | electrochemical | 0-50 or 0-2,000 ppm | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-SO2 | electrochemical | 0-50 or 0-2,000 ppm | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2638-SO2 · multi-option IP65, E2639-SO2 · 3 relays, buzzer, E2608-SO2 · 2 relays, wall/duct, E2618-SO2 · transmitter, no relays, E2648-SO2 · aluminium IP66 |
|---|
Official Evikon documents, kept up to date by the manufacturer: