Nitrogen dioxide (NO2) gas detector

Fixed nitrogen dioxide (NO2) detectors for car parks, loading bays and warehouses with diesel engines: electrochemical cell from 0-10 to 0-200 ppm, from −30 to +50 °C. 4-20 mA transmitters for ventilation or relay alarms. Choose the model below to see its specifications and options.

Request a quote

SKU: N/A Category:
Description

Fixed nitrogen dioxide (NO2) detectors for car parks, loading bays and warehouses with diesel engines: electrochemical cell from 0-10 to 0-200 ppm, from −30 to +50 °C. 4-20 mA transmitters for ventilation or relay alarms.

Why detect NO2?

Nitrogen dioxide (NO2) comes mainly from diesel engines: trucks at the docks, forklifts, generator sets. Heavier than air, it strongly irritates the airways. In car parks and closed loading bays, it is measured together with carbon monoxide to control the ventilation.

The sensor

Electrochemical cell, 0-10, 0-20 or 0-200 ppm ranges depending on the model, operation from −30 to +50 °C (−20 °C on 0-200 ppm), response time under 60 s, lifetime over 2 years, checked every 6 months.

Where to install a NO2 detector?

Near the sources (loading bays, manoeuvring areas, generator sets), slightly below breathing height, away from supply air outlets. The number of points depends on the area and the ventilation of the room.

Available models

Model Sensor Ranges Housing Outputs Local alarm
E2638-NO2 electrochemical 0-20 or 0-200 ppm grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2639-NO2 electrochemical 0-20 or 0-200 ppm grey ABS, IP65, 190 mm wide 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs
E2608-NO2 electrochemical 0-20 or 0-200 ppm grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2618-NO2 electrochemical 0-20 or 0-200 ppm grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2648-NO2 electrochemical 0-20 or 0-200 ppm die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2630-NO2 electrochemical 0-10 ppm grey ABS, IP65, 145 mm wide no analog output (UART) 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test
E2617-NO2 electrochemical 0-10 or 0-20 ppm ABS, IP65, 82 × 94 × 35 mm 1 × 4-20 mA or 0-10 V none: alarm handled by the PLC

Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.

Alarm and options by model

  • E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
  • E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
  • E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
  • E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
  • E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
  • E2630 : 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test ; 24 V or 230 V power supply.
  • E2617 : none: alarm handled by the PLC ; none.

Request a quote

Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.

See all our gas detectors and sensors.

Additional information
ModelE2638-NO2 · multi-option IP65, E2639-NO2 · 3 relays, buzzer, E2608-NO2 · 2 relays, wall/duct, E2618-NO2 · transmitter, no relays, E2648-NO2 · aluminium IP66, E2630-NO2 · IP65 alarm, buzzer, E2617-NO2 · low-cost transmitter