Afric Froid supplies and installs refrigeration condensing units for chilled and frozen cold rooms, cold stores and blast freezers. Our range runs from compact Danfoss Optyma units of a few kilowatts to housed Bock units with one or two compressors, with condensers sized for hot climates.

Showing all 5 results

Housed condensing unit

Afric Froid housed condensing unit built with one or two Bock semi-hermetic compressors, for chilled or frozen cold rooms.

  • 10 compressor sizes, from Bock HG34e/315 to HG66e/2070, with 1 or 2 compressors per unit
  • Medium-temperature (chilled) or low-temperature (frozen) version
  • Condenser sized for hot climates, with optional EC fans and Danfoss controller for floating condensing
  • Quoted per project, installed and serviced by our teams

Housed screw condensing unit

Our housed condensing units with screw compressors deliver powerful, consistent cooling. They are ideal for frozen storage cold rooms at

Bock Plusbox condensing unit

Bock Plusbox housed condensing unit, ready for outdoor installation, with a Bock HG34e 4-cylinder semi-hermetic compressor in a sound-proofed enclosure: 8 models (standard or more powerful S motor), from 9.0 to 15.9 kW with R449A (−10 °C, 32 °C ambient) and 6.5 to 15 hp (CV).

Bock open condensing unit

BOCK offers a complete range of condensing units with receivers (units with
suction-gas-cooled HG compressors). These compressors are used in the segment of
low- to medium-capacity machines. All units follow a design principle
modular.

Cooling capacity: 2 to 49 kW (-5°C/43°C)

Number of pistons: 2 to 6

Six series and 37 models (standard L or more powerful SL motor), from 2.8 to 49.7 kW with R404A (−5 °C / +43 °C ambient) and 3 to 52 hp (CV). Choose your series:

📄 Download the PDF brochure

Danfoss Optyma Slim Pack condensing unit

The Danfoss Optyma™ Slim Pack outdoor condensing unit comes for medium temperature (8 models, MLZ scroll compressors, 3.2 to 10.4 kW) and for low temperature (5 models, NTZ and LLZ compressors, 1.4 to 4.7 kW), with R404A at 43 °C ambient, 230 V or 400 V. Choose your application:

Optyma unit benefits:

  • Compact system with a minimal footprint, for easy handling, shipping and installation,
  • Easy access to all components for easier servicing and simpler maintenance,
  • Quiet scroll compressor.

What is a condensing unit?

A condensing unit combines the compressor, the air-cooled condenser, the liquid receiver and the safety controls on one frame. It sits outdoors or in a plant room and feeds one or more evaporators (unit coolers) inside the cold room.

The compressor draws in the evaporated refrigerant and compresses it. The condenser rejects the heat to the outside air. The liquid refrigerant then returns to the expansion valve of the evaporator.

Our cold room condensing units

RangeCompressorCooling capacityTypical use
Danfoss Optyma Slim PackDanfoss scroll3.2 to 10.4 kW chilled, 1.4 to 4.7 kW frozen (R404A, 43 °C ambient)small and medium cold rooms, shops
Bock PlusboxBock HGX34e reciprocating9 to 15.9 kW (R449A, −10 °C, 32 °C ambient)compact housed unit
Bock open condensing unitBock HGX12P to HGX66e reciprocating2.8 to 49.7 kW (R404A, −5 °C, 43 °C ambient)installed in a plant room
Afric Froid housed condensing unit1 or 2 Bock reciprocating compressors, HG34e/315 to HG66e/2070Per compressor, R404A: 13.7 to 96.5 kW chilled (−6 °C / +48 °C), 5.1 to 38.2 kW frozen (−26 °C / +46 °C)cold rooms and cold stores, chilled or frozen version
Housed screw condensing unitBitzer screw with economisersized per projectfrozen stores at −20 to −25 °C, blast freezers
Refrigeration racksseveral Bock or Bitzer compressorssized per projectcold stores with several rooms

Chilled or frozen cold rooms

A chilled cold room (fruit, vegetables, dairy, drinks) needs a medium-temperature unit. A frozen cold room (frozen meat and fish, ice cream) needs a low-temperature unit.

On our housed units, the same Bock compressor can serve both. What changes is the condenser, the pipe sizes and some accessories, such as the oil separator added on low-temperature units. For large frozen stores at −25 °C and blast freezers, we offer Bitzer screw units.

Built for hot climates

In Ghana, West Africa and North Africa, outdoor air often goes above 40 °C in the hot season. A unit selected for a temperate climate then loses capacity and trips on high pressure.

Our housed units use condensers sized for hot countries, with a 10 K difference between air and condensing temperature. Where Danfoss and Bock publish them, the capacities we show are at 43 °C ambient. The refrigerant is chosen for the application and for what is available locally: R404A, R449A, R452A, or R134a for large chilled stores.

As an option, our housed units can be fitted with EC fans and a Danfoss electronic controller for floating condensing. The unit then uses less power as soon as the air cools down, at night or in the cooler season, and runs more quietly.

How to size a condensing unit for a cold room

The capacity comes from the heat load of the cold room. It depends on volume, insulation, product, daily product intake and its temperature, door openings and outdoor temperature. Two 20 m³ cold rooms can need very different units if one receives warm produce every day.

Our cold room heat load calculator gives a first estimate in a few minutes. Our engineers then confirm the condensing unit and evaporator selection.

Supply and installation in Ghana and across Africa

Afric Froid designs, supplies, installs and commissions condensing units in Ghana, Tunisia, Senegal and Côte d’Ivoire. Other English-speaking African countries are studied on request. Our Bock and Bitzer units run in cold stores in Tripoli, frozen storage rooms in Abidjan, blast freezers in Dakar and potato cold rooms in Ouahigouya.

Frequently asked questions

Housed or open condensing unit?

A housed unit goes outdoors: its casing protects the components from rain and sun and reduces noise. An open unit is installed in a ventilated plant room.

Which condensing unit for a freezer room?

A low-temperature unit, with an oil separator and suitable pipe sizes. For large volumes at −25 °C and blast freezers, a screw unit is often the better choice.

Which refrigerant should I choose?

R404A is still widely used in Africa. R449A and R452A have a lower global warming potential. The choice also depends on which refrigerants service teams can get locally.

Do you deliver to Ghana?

Yes. We supply and install condensing units in Ghana, and we study projects in other English-speaking African countries on request.

What is the price of a cold room condensing unit?

It depends on capacity, temperature, refrigerant and options. We quote each unit individually: request a quote.