Ammonia (NH3) gas detector (R717)

Fixed ammonia NH3 (R717) detectors for ammonia machinery rooms, refrigeration plants and cold rooms: electrochemical sensors from 0-100 to 0-5,000 ppm or catalytic sensors in % vol, 4-20 mA outputs, Modbus and alarm relays. Choose the model below to see its specifications and options.

Request a quote

SKU: N/A Category:
Description

Fixed ammonia NH3 (R717) detectors for ammonia machinery rooms, refrigeration plants and cold rooms: electrochemical sensors from 0-100 to 0-5,000 ppm or catalytic sensors in % vol, 4-20 mA outputs, Modbus and alarm relays.

Why detect ammonia?

Ammonia (R717) is an excellent refrigerant with no effect on the ozone layer or the climate, widely used in large industrial plants. It is, however, toxic, and flammable at high concentration. Its pungent smell is noticed at a few ppm, but people get used to it and it says nothing about the real concentration: only a fixed detector allows a timely reaction, day and night. The EN 378-3 standard also requires gas detection in machinery rooms and in rooms where a leak may exceed the practical limit of the refrigerant.

ppm or % vol: two types of sensors

  • Electrochemical sensor (NH3-E versions): it measures low concentrations, from 0-100 to 0-5,000 ppm, to protect people and start ventilation at the very beginning of a leak. It works from −40 to +50 °C, so also in freezer rooms. Factory set-points on the 0-100 ppm range: 25 and 35 ppm. Checked every 6 months, lifetime over 2 years.
  • Catalytic bead sensor (NH3-P versions): it measures from 0 to 15 % vol, i.e. 0-100 % of the lower explosive limit. It monitors the explosion risk in case of a major leak, in addition to the ppm sensor. It works from −10 °C only.

In a machinery room, both are often combined: an electrochemical sensor for alarm and ventilation, a catalytic sensor for the emergency shutdown of the plant.

Where to install an ammonia detector?

Ammonia is lighter than air: it rises. Install the detectors high up, above compressors, separators, valves and evaporators, and near air extraction points. In cold rooms, place them near the evaporators, away from doors and air curtains. A permanently ammonia-laden atmosphere wears the electrochemical cell: the detector belongs where the air is normally clean.

Useful options

  • alarm and ventilation relays, buzzer and LEDs, or three relays (pre-alarm, alarm, fault) on the E2639;
  • remote probe to measure inside the cold room with the electronics outside;
  • IP66 aluminium housing (E2648) for wash-down rooms, flameproof enclosure (E2670) for ATEX zones 2 and 22.

Available models

Model Sensor Ranges Housing Outputs Local alarm
E2638-NH3-E electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2638-NH3-P catalytic bead (pellistor) 0-15 % vol, i.e. 0-100 % LEL (narrower scale possible, e.g. 0-4 % vol) grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2639-NH3 electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) grey ABS, IP65, 190 mm wide 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs
E2608-NH3-E electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2608-NH3-P catalytic bead (pellistor) 0-15 % vol, i.e. 0-100 % LEL (narrower scale possible, e.g. 0-4 % vol) grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2618-NH3-E electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2618-NH3-P catalytic bead (pellistor) 0-15 % vol, i.e. 0-100 % LEL (narrower scale possible, e.g. 0-4 % vol) grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2648-NH3-E electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2648-NH3-P catalytic bead (pellistor) 0-15 % vol, i.e. 0-100 % LEL (narrower scale possible, e.g. 0-4 % vol) die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2670-NH3-E electrochemical 0-100, 0-300, 0-1,000 or 0-5,000 ppm (10,000 ppm on request) flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2670-NH3-P catalytic bead (pellistor) 0-15 % vol, i.e. 0-100 % LEL (narrower scale possible, e.g. 0-4 % vol) flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A

Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.

Alarm and options by model

  • E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
  • E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
  • E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
  • E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
  • E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
  • E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.

Request a quote

Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.

See all our gas detectors and sensors.

Additional information
ModelE2638-NH3-E · ppm · multi-option IP65, E2638-NH3-P · % vol · multi-option IP65, E2639-NH3 · ppm · 3 relays, buzzer, E2608-NH3-E · ppm · 2 relays, wall/duct, E2608-NH3-P · % vol · 2 relays, wall/duct, E2618-NH3-E · ppm · transmitter, no relays, E2618-NH3-P · % vol · transmitter, no relays, E2648-NH3-E · ppm · aluminium IP66, E2648-NH3-P · % vol · aluminium IP66, E2670-NH3-E · ppm · ATEX zones 2/22, E2670-NH3-P · % vol · ATEX zones 2/22