Refrigerant gas detector (HFC, HFO, R32, R290)

Fixed refrigerant gas detectors for racks, condensing units, heat pumps and cold rooms: HFC and HFO (R404A, R134a, R410A, R449A, R448A…), A2L (R32, R454B, R1234ze) and propane R290. 4-20 mA outputs, Modbus and relays. Choose the model below to see its specifications and options.

Request a quote

SKU: N/A Category:
Description

Fixed refrigerant gas detectors for racks, condensing units, heat pumps and cold rooms: HFC and HFO (R404A, R134a, R410A, R449A, R448A…), A2L (R32, R454B, R1234ze) and propane R290. 4-20 mA outputs, Modbus and relays.

Fixed or portable detector?

A portable leak detector is used by the refrigeration technician to locate a leak during a service visit. A fixed detector stays in place and monitors the room permanently: it raises the alarm as soon as a leak starts, triggers ventilation and keeps a record of the readings. This is what machinery room safety rules require, and it limits refrigerant losses, which are increasingly expensive.

Refrigerants and sensors

  • Non-flammable HFCs and HFOs (R404A, R134a, R407C, R410A, R449A, R507, R513A…): semiconductor sensor, 0-1,000 or 0-2,500 ppm ranges, minimum alarm set-point 250 ppm, operation from −30 to +60 °C, yearly check. It responds to most halogenated refrigerants: state the refrigerant of your system for the set-up.
  • Mildly flammable A2L (R32, R454A, R454B, R454C, R1234ze): semiconductor sensor on the E2608 to E2670 series, or calibration-free infrared sensor on the E2674, measured in % of the lower flammability limit.
  • A3 hydrocarbons (propane R290, propylene R1270, isobutane): infrared sensor of the E2674, or combustible gas sensor (LEL versions) calibrated on propane when ordered.

Ammonia and CO2 have their own sensors: see our ammonia detectors and our CO2 detectors.

Where to install a refrigerant detector?

HFC and HFO refrigerants and propane are heavier than air: they collect near the floor and in low points. Install the detector low, near compressors, receivers, valves and evaporators, and in pits or trenches if any. In an R290 or R32 heat pump or water chiller, the E2674 mounts directly inside the cabinet, on a DIN rail.

Regulations

EN 378-3 requires gas detection in machinery rooms and in rooms where a leak could exceed the practical limit of the refrigerant. In Europe, the F-Gas regulation also requires leak detection systems on large HFC installations. We help you define the number of detection points and the set-points.

Available models

Model Sensor Ranges Housing Outputs Local alarm
E2638-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2639-HFC MOS semiconductor or infrared (IR code) 0-1,000 or 0-2,500 ppm grey ABS, IP65, 190 mm wide 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs
E2608-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2618-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2648-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2670-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2630-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm grey ABS, IP65, 145 mm wide no analog output (UART) 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test
E2610-HFC metal-oxide semiconductor (MOS), infrared on request 0-1,000 or 0-2,500 ppm slotted ABS, IP20, 85 × 85 × 37 mm, dry rooms no analog output (UART) 2 SPDT relays 5 A, LED and 85 dB buzzer
E2674E NDIR infrared, automatic recalibration every 72 h 0-50 % LFL, alarm at 10 % aluminium, IP54, 89 × 58 × 39 mm, DIN rail or wall 3 electronic outputs, 300 mA, 36 VDC; Modbus RS485 see outputs
E2674R NDIR infrared, automatic recalibration every 72 h 0-50 % LFL, alarm at 10 % aluminium, IP54, 89 × 58 × 39 mm, DIN rail or wall 2 SPDT relays, 1 A, 36 V; Modbus RS485 see outputs

Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.

Alarm and options by model

  • E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
  • E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
  • E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
  • E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
  • E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
  • E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.
  • E2630 : 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test ; 24 V or 230 V power supply.
  • E2610 : 2 SPDT relays 5 A, LED and 85 dB buzzer ; 24 V or 230 V power supply.

Request a quote

Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.

See all our gas detectors and sensors.

Additional information
ModelE2638-HFC · multi-option IP65, E2639-HFC · 3 relays, buzzer, E2608-HFC · 2 relays, wall/duct, E2618-HFC · transmitter, no relays, E2648-HFC · aluminium IP66, E2670-HFC · ATEX zones 2/22, E2630-HFC · IP65 alarm, buzzer, E2610-HFC · compact IP20 alarm, E2674E · infrared, 3 outputs, E2674R · infrared, 2 relays