Combustible gas detector (methane, LPG, propane)

Fixed combustible and explosive gas detectors for boiler rooms, industrial kitchens, propane rooms and machinery rooms: methane, natural gas, propane, butane, LPG, hydrogen, measured from 0 to 100 % LEL. Stand-alone alarms or 4-20 mA transmitters. Choose the model below to see its specifications and options.

Request a quote

SKU: N/A Category:
Description

Fixed combustible and explosive gas detectors for boiler rooms, industrial kitchens, propane rooms and machinery rooms: methane, natural gas, propane, butane, LPG, hydrogen, measured from 0 to 100 % LEL. Stand-alone alarms or 4-20 mA transmitters.

Why detect combustible gases?

A natural gas, propane or butane leak in a closed room can create an explosive mixture. The detector measures the concentration as a percentage of the lower explosive limit (LEL): 100 % LEL is the level above which the mixture can ignite. Alarm set-points are placed well below, usually 10 or 20 % LEL for the pre-alarm and 25 to 50 % LEL for the alarm, with closing of the gas solenoid valve and start of ventilation.

Sensors

  • Metal-oxide semiconductor (MOS): rugged and cost-effective, from −40 to +70 °C, lifetime over 5 years, yearly check. It equips most Evikon combustible gas detectors.
  • Catalytic bead (pellistor): fast response (10 s) and linear reading, from −10 to +50 °C, checked every 6 months. It is available on request, and as standard on the E2617.
  • Infrared: for flammable refrigerants (R290, R1270, R32), see the calibration-free E2674.

Evikon combustible gas detectors are calibrated on methane by default. For propane, butane, LPG or hydrogen, state the gas when ordering: the set-up depends on the gas.

Where to install a combustible gas detector?

Natural gas (methane) is lighter than air: install the detector high up, about 30 cm below the ceiling, above burners and appliances. Propane, butane and LPG are heavier than air: install the detector low, about 30 cm above the floor, near leak points. Avoid areas with cooking fumes and cleaning products, which may distort the reading.

Stand-alone alarm or transmitter?

For a boiler room or a kitchen, a stand-alone relay alarm is often enough: the IP65 E2630 or the E2610 for dry rooms. For a supervised site, choose a 4-20 mA / Modbus transmitter (E2608, E2618, E2638, E2639, E2648). In ATEX zone 2 or 22, use the flameproof E2670.

Available models

Model Sensor Ranges Housing Outputs Local alarm
E2638-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2638-CH4 MOS, or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 90 × 145 × 55 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display
E2639-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 190 mm wide 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs
E2608-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2608-CH4 MOS, or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 87 × 82 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU 2 SPST relays 5 A
E2618-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2618-CH4 MOS, or catalytic bead (pellistor) on request 0-100 % LEL grey ABS, IP65, 82 × 80 × 55 mm, wall or duct 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU none: alarm handled by the PLC
E2648-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2648-CH4 MOS, or catalytic bead (pellistor) on request 0-100 % LEL die-cast aluminium, IP66, 120 × 125 × 57 mm 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2670-LEL metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request 0-100 % LEL flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU optional 2 SPST relays 5 A
E2630-LEL metal-oxide semiconductor (MOS) 0-100 % LEL grey ABS, IP65, 145 mm wide no analog output (UART) 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test
E2610-LEL metal-oxide semiconductor (MOS) 0-100 % LEL slotted ABS, IP20, 85 × 85 × 37 mm, dry rooms no analog output (UART) 2 SPDT relays 5 A, LED and 85 dB buzzer
E2617-LEL catalytic bead (pellistor) 0-100 % LEL ABS, IP65, 82 × 94 × 35 mm 1 × 4-20 mA or 0-10 V none: alarm handled by the PLC

Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.

Alarm and options by model

  • E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
  • E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
  • E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
  • E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
  • E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
  • E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.
  • E2630 : 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test ; 24 V or 230 V power supply.
  • E2610 : 2 SPDT relays 5 A, LED and 85 dB buzzer ; 24 V or 230 V power supply.
  • E2617 : none: alarm handled by the PLC ; none.

Request a quote

Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.

See all our gas detectors and sensors.

Additional information
ModelE2638-LEL · LEL · multi-option IP65, E2638-CH4 · methane · multi-option IP65, E2639-LEL · LEL · 3 relays, buzzer, E2608-LEL · LEL · 2 relays, wall/duct, E2608-CH4 · methane · 2 relays, wall/duct, E2618-LEL · LEL · transmitter, no relays, E2618-CH4 · methane · transmitter, no relays, E2648-LEL · LEL · aluminium IP66, E2648-CH4 · methane · aluminium IP66, E2670-LEL · LEL · ATEX zones 2/22, E2630-LEL · LEL · IP65 alarm, buzzer, E2610-LEL · LEL · compact IP20 alarm, E2617-LEL · LEL · low-cost transmitter