CO2 gas detector (R744)
Fixed CO2 detectors with infrared sensor for CO2 (R744) refrigeration systems, ripening rooms, controlled atmosphere stores, cellars and breweries: 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol, from −40 to +60 °C. Choose the model below to see its specifications and options.
Fixed CO2 detectors with infrared sensor for CO2 (R744) refrigeration systems, ripening rooms, controlled atmosphere stores, cellars and breweries: 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol, from −40 to +60 °C.
An industrial CO2 detector, not an air quality monitor
The small CO2 monitors sold for offices and schools measure indoor air quality up to a few thousand ppm. A CO2 (R744) refrigeration system, a ripening room or a controlled atmosphere store needs an industrial detector: measurement up to 40,000 ppm or 5 % vol, operation in cold and humid conditions, 4-20 mA outputs and alarm relays.
Why monitor CO2?
CO2 is odourless and heavier than air. In case of a leak, it collects near the floor and displaces oxygen: at high concentration it causes headaches, discomfort and then asphyxia. The occupational exposure limit commonly used in Europe is 5,000 ppm over 8 hours. CO2 is also a production parameter: in ripening rooms and controlled atmosphere stores, its level is precisely controlled.
The infrared sensor
Evikon detectors measure CO2 by NDIR infrared or photoacoustic sensing, a stable optical measurement that does not wear like a chemical cell:
- three ranges: 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol, up to 100 % vol on request;
- operation from −40 to +60 °C and up to 100 % humidity: suitable for freezer rooms;
- lifetime of about 10 years, no field recalibration thanks to the ABC self-correction on the ppm ranges;
- ambient pressure compensation as an option on some series.
Where to install a CO2 detector?
As CO2 is heavier than air, install the detector low, about thirty centimetres above the floor, near compressors, valves and evaporators, and in low points where the gas may stagnate. In CO2 cold rooms, plan one detector in each room and one in the machinery room.
For controlled atmosphere, combine it with an oxygen detector and, in ripening rooms, with an ethylene detector.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2638-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2639-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2608-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2670-CO2 | NDIR infrared or photoacoustic | 0-10,000 ppm, 0-40,000 ppm or 0-5 % vol (up to 100 % vol on request) | flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
- E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2638-CO2 · multi-option IP65, E2639-CO2 · 3 relays, buzzer, E2608-CO2 · 2 relays, wall/duct, E2618-CO2 · transmitter, no relays, E2648-CO2 · aluminium IP66, E2670-CO2 · ATEX zones 2/22 |
|---|
Official Evikon documents, kept up to date by the manufacturer: