Refrigerant gas detector (HFC, HFO, R32, R290)
Fixed refrigerant gas detectors for racks, condensing units, heat pumps and cold rooms: HFC and HFO (R404A, R134a, R410A, R449A, R448A…), A2L (R32, R454B, R1234ze) and propane R290. 4-20 mA outputs, Modbus and relays. Choose the model below to see its specifications and options.
Fixed refrigerant gas detectors for racks, condensing units, heat pumps and cold rooms: HFC and HFO (R404A, R134a, R410A, R449A, R448A…), A2L (R32, R454B, R1234ze) and propane R290. 4-20 mA outputs, Modbus and relays.
Fixed or portable detector?
A portable leak detector is used by the refrigeration technician to locate a leak during a service visit. A fixed detector stays in place and monitors the room permanently: it raises the alarm as soon as a leak starts, triggers ventilation and keeps a record of the readings. This is what machinery room safety rules require, and it limits refrigerant losses, which are increasingly expensive.
Refrigerants and sensors
- Non-flammable HFCs and HFOs (R404A, R134a, R407C, R410A, R449A, R507, R513A…): semiconductor sensor, 0-1,000 or 0-2,500 ppm ranges, minimum alarm set-point 250 ppm, operation from −30 to +60 °C, yearly check. It responds to most halogenated refrigerants: state the refrigerant of your system for the set-up.
- Mildly flammable A2L (R32, R454A, R454B, R454C, R1234ze): semiconductor sensor on the E2608 to E2670 series, or calibration-free infrared sensor on the E2674, measured in % of the lower flammability limit.
- A3 hydrocarbons (propane R290, propylene R1270, isobutane): infrared sensor of the E2674, or combustible gas sensor (LEL versions) calibrated on propane when ordered.
Ammonia and CO2 have their own sensors: see our ammonia detectors and our CO2 detectors.
Where to install a refrigerant detector?
HFC and HFO refrigerants and propane are heavier than air: they collect near the floor and in low points. Install the detector low, near compressors, receivers, valves and evaporators, and in pits or trenches if any. In an R290 or R32 heat pump or water chiller, the E2674 mounts directly inside the cabinet, on a DIN rail.
Regulations
EN 378-3 requires gas detection in machinery rooms and in rooms where a leak could exceed the practical limit of the refrigerant. In Europe, the F-Gas regulation also requires leak detection systems on large HFC installations. We help you define the number of detection points and the set-points.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2638-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2639-HFC | MOS semiconductor or infrared (IR code) | 0-1,000 or 0-2,500 ppm | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2608-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2670-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2630-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | grey ABS, IP65, 145 mm wide | no analog output (UART) | 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test |
| E2610-HFC | metal-oxide semiconductor (MOS), infrared on request | 0-1,000 or 0-2,500 ppm | slotted ABS, IP20, 85 × 85 × 37 mm, dry rooms | no analog output (UART) | 2 SPDT relays 5 A, LED and 85 dB buzzer |
| E2674E | NDIR infrared, automatic recalibration every 72 h | 0-50 % LFL, alarm at 10 % | aluminium, IP54, 89 × 58 × 39 mm, DIN rail or wall | 3 electronic outputs, 300 mA, 36 VDC; Modbus RS485 | see outputs |
| E2674R | NDIR infrared, automatic recalibration every 72 h | 0-50 % LFL, alarm at 10 % | aluminium, IP54, 89 × 58 × 39 mm, DIN rail or wall | 2 SPDT relays, 1 A, 36 V; Modbus RS485 | see outputs |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
- E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.
- E2630 : 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test ; 24 V or 230 V power supply.
- E2610 : 2 SPDT relays 5 A, LED and 85 dB buzzer ; 24 V or 230 V power supply.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2638-HFC · multi-option IP65, E2639-HFC · 3 relays, buzzer, E2608-HFC · 2 relays, wall/duct, E2618-HFC · transmitter, no relays, E2648-HFC · aluminium IP66, E2670-HFC · ATEX zones 2/22, E2630-HFC · IP65 alarm, buzzer, E2610-HFC · compact IP20 alarm, E2674E · infrared, 3 outputs, E2674R · infrared, 2 relays |
|---|
Official Evikon documents, kept up to date by the manufacturer:
Related products
Oxygen (O2) gas detector
Carbon monoxide (CO) gas detector
Fixed carbon monoxide (CO) detectors for car parks, loading bays, warehouses with combustion-engine forklifts and boiler rooms: electrochemical cell from 0-100 to 0-1,000 ppm, lifetime over 10 years. Relay and buzzer alarms, or 4-20 mA transmitters for ventilation control. Choose the model below to see its specifications and options.