Hydrogen (H2) gas detector
Fixed hydrogen H2 detectors for forklift battery charging rooms, battery and UPS rooms, data centres and energy storage: 0-100 % LEL measurement, detection of lithium-ion battery off-gassing. Choose the model below to see its specifications and options.
Fixed hydrogen H2 detectors for forklift battery charging rooms, battery and UPS rooms, data centres and energy storage: 0-100 % LEL measurement, detection of lithium-ion battery off-gassing.
Where does hydrogen come from?
Lead-acid batteries of forklifts, pallet trucks and UPS systems release hydrogen while charging, especially at the end of charge or when overcharged. Lithium-ion batteries release hydrogen, electrolyte vapours and carbon monoxide at the beginning of thermal runaway. Hydrogen is colourless, odourless, very light and flammable from 4 % in air: in a poorly ventilated charging room it can build up under the ceiling until it forms an explosive mixture.
Two ways to detect it
- E2673 / E2673A off-gassing detector: thermal conductivity hydrogen sensor (0-100 % LEL), electrolyte vapour sensor, humidity and temperature measurement and, on the E2673A, carbon monoxide. About 15 years without maintenance or field calibration, DIN rail, suitable for ATEX zone 2. It is the choice for battery rooms, UPS rooms and energy storage containers.
- Combustible gas detector calibrated on hydrogen: the LEL versions of the E2608, E2618, E2638, E2639, E2648 and E2670 series measure hydrogen from 0 to 100 % LEL when specified at order (for example E2639-LEL-H2). They suit forklift charging rooms, with relays for ventilation.
Where to install a hydrogen detector?
Hydrogen rises immediately: install the detector at the highest point of the room, above the charging stations and near air extraction points, never near the floor. Connect its relays to the room ventilation and, if possible, to the charger shutdown.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2673 | NDIR infrared | hydrogen 0-100 % LEL, VOC (index 0-500) | anodised aluminium, IP40, DIN rail | 3 relays, Modbus RS485 | see outputs |
| E2673A | NDIR infrared | hydrogen 0-100 % LEL, VOC (index 0-500), carbon monoxide 0-300 or 0-1,000 ppm | anodised aluminium, IP40, DIN rail | 3 relays, Modbus RS485 | see outputs |
| E2639-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2638-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2608-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2670-LEL (H2) | metal-oxide semiconductor (MOS), or catalytic bead (pellistor) on request | 0-100 % LEL | flameproof aluminium (Ex d), IP65, 155 × 145 × 110 mm; II 3G Ex d IIC T6 Gc, II 3D Ex tb IIIB T85 °C Dc (zones 2 and 22) | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
- E2670 : optional 2 SPST relays 5 A ; relays, glands on both sides, 24 VAC or 230 VAC; armoured cables or ATEX conduits.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2673 · H2, VOC, RH/T, E2673A · H2, VOC, CO, RH/T, E2639-LEL · H2 · 3 relays, buzzer, E2638-LEL · H2 · multi-option IP65, E2608-LEL · H2 · 2 relays, wall/duct, E2618-LEL · H2 · transmitter, no relays, E2648-LEL · H2 · aluminium IP66, E2670-LEL · H2 · ATEX zones 2/22 |
|---|
Official Evikon documents, kept up to date by the manufacturer:
Related products
Ethylene (C2H4) gas detector
Combustible gas detector (methane, LPG, propane)
Fixed combustible and explosive gas detectors for boiler rooms, industrial kitchens, propane rooms and machinery rooms: methane, natural gas, propane, butane, LPG, hydrogen, measured from 0 to 100 % LEL. Stand-alone alarms or 4-20 mA transmitters. Choose the model below to see its specifications and options.