Nitrogen dioxide (NO2) gas detector
Fixed nitrogen dioxide (NO2) detectors for car parks, loading bays and warehouses with diesel engines: electrochemical cell from 0-10 to 0-200 ppm, from −30 to +50 °C. 4-20 mA transmitters for ventilation or relay alarms. Choose the model below to see its specifications and options.
Fixed nitrogen dioxide (NO2) detectors for car parks, loading bays and warehouses with diesel engines: electrochemical cell from 0-10 to 0-200 ppm, from −30 to +50 °C. 4-20 mA transmitters for ventilation or relay alarms.
Why detect NO2?
Nitrogen dioxide (NO2) comes mainly from diesel engines: trucks at the docks, forklifts, generator sets. Heavier than air, it strongly irritates the airways. In car parks and closed loading bays, it is measured together with carbon monoxide to control the ventilation.
The sensor
Electrochemical cell, 0-10, 0-20 or 0-200 ppm ranges depending on the model, operation from −30 to +50 °C (−20 °C on 0-200 ppm), response time under 60 s, lifetime over 2 years, checked every 6 months.
Where to install a NO2 detector?
Near the sources (loading bays, manoeuvring areas, generator sets), slightly below breathing height, away from supply air outlets. The number of points depends on the area and the ventilation of the room.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2638-NO2 | electrochemical | 0-20 or 0-200 ppm | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2639-NO2 | electrochemical | 0-20 or 0-200 ppm | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2608-NO2 | electrochemical | 0-20 or 0-200 ppm | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-NO2 | electrochemical | 0-20 or 0-200 ppm | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-NO2 | electrochemical | 0-20 or 0-200 ppm | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2630-NO2 | electrochemical | 0-10 ppm | grey ABS, IP65, 145 mm wide | no analog output (UART) | 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test |
| E2617-NO2 | electrochemical | 0-10 or 0-20 ppm | ABS, IP65, 82 × 94 × 35 mm | 1 × 4-20 mA or 0-10 V | none: alarm handled by the PLC |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
- E2630 : 2 SPDT relays 5 A, LED and 85 dB buzzer, magnetic key test ; 24 V or 230 V power supply.
- E2617 : none: alarm handled by the PLC ; none.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2638-NO2 · multi-option IP65, E2639-NO2 · 3 relays, buzzer, E2608-NO2 · 2 relays, wall/duct, E2618-NO2 · transmitter, no relays, E2648-NO2 · aluminium IP66, E2630-NO2 · IP65 alarm, buzzer, E2617-NO2 · low-cost transmitter |
|---|
Official Evikon documents, kept up to date by the manufacturer:
Related products
Ammonia (NH3) gas detector (R717)
Refrigerant gas detector (HFC, HFO, R32, R290)
Ethylene (C2H4) gas detector
Hydrogen (H2) gas detector
Carbon monoxide (CO) gas detector
Fixed carbon monoxide (CO) detectors for car parks, loading bays, warehouses with combustion-engine forklifts and boiler rooms: electrochemical cell from 0-100 to 0-1,000 ppm, lifetime over 10 years. Relay and buzzer alarms, or 4-20 mA transmitters for ventilation control. Choose the model below to see its specifications and options.