Oxygen (O2) gas detector
Fixed oxygen O2 detectors for controlled atmosphere stores and nitrogen, CO2 or inert gas rooms: 0-25 % vol measurement, oxygen deficiency alarm at 19.5 %, 2, 3 or 5-year electrochemical cell. Choose the model below to see its specifications and options.
Fixed oxygen O2 detectors for controlled atmosphere stores and nitrogen, CO2 or inert gas rooms: 0-25 % vol measurement, oxygen deficiency alarm at 19.5 %, 2, 3 or 5-year electrochemical cell.
The danger of oxygen deficiency
Air contains 20.9 % oxygen. When an inert gas (nitrogen, CO2, argon) displaces it, the drop can neither be seen nor smelled: below 19.5 % it is already called oxygen deficiency, and below about 10 % loss of consciousness can be very fast. Controlled atmosphere stores, nitrogen generator rooms, CO2 or dry ice storage and liquid nitrogen freezing rooms must therefore be equipped with oxygen detectors.
Controlled atmosphere: a production and safety measurement
In apple, pear or kiwi storage, the oxygen level of the room is deliberately lowered to a few per cent to slow down fruit respiration. The oxygen detector then has two jobs: it monitors the set-point during storage, and it protects the staff who must enter the room or work nearby. Combine it with a CO2 detector, the other gas of controlled atmosphere.
The Evikon sensor
- electrochemical cell, 0-25 % vol measurement, 0.01 % resolution;
- three lifetimes to choose from: over 2, 3 or 5 years (O2-3Y and O2-5Y codes);
- operation from −30 to +50 °C, or −40 to +60 °C with the 5-year cell;
- response time under 10 s; factory alarm at 19.5 % vol; checked every 6 months;
- 4-20 mA / 0-10 V outputs, Modbus and relays depending on the series; the E2617 is a cost-effective single-output version for building management.
Where to install an oxygen detector?
Install it at breathing height (about 1.5 m) in rooms where people work, and near the floor if the gas that may displace oxygen is heavier than air, such as CO2. Fit a remote alarm at the room entrance so that nobody enters during an alarm.
Available models
| Model | Sensor | Ranges | Housing | Outputs | Local alarm |
|---|---|---|---|---|---|
| E2638-O2 | electrochemical (2, 3 or 5-year cell) | 0-25 % vol | grey ABS, IP65, 90 × 145 × 55 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display |
| E2639-O2 | electrochemical (2, 3 or 5-year cell) | 0-25 % vol | grey ABS, IP65, 190 mm wide | 2 × 4-20 mA, RS485 Modbus RTU, optional WiFi | 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs |
| E2608-O2 | electrochemical (2, 3 or 5-year cell) | 0-25 % vol | grey ABS, IP65, 87 × 82 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | 2 SPST relays 5 A |
| E2618-O2 | electrochemical (2, 3 or 5-year cell) | 0-25 % vol | grey ABS, IP65, 82 × 80 × 55 mm, wall or duct | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | none: alarm handled by the PLC |
| E2648-O2 | electrochemical (2, 3 or 5-year cell) | 0-25 % vol | die-cast aluminium, IP66, 120 × 125 × 57 mm | 2 × 4-20 mA / 0-10 V, RS485 Modbus RTU | optional 2 SPST relays 5 A |
| E2617-O2 | electrochemical | 0-25 % vol | ABS, IP65, 82 × 94 × 35 mm | 1 × 4-20 mA or 0-10 V | none: alarm handled by the PLC |
Choose the model in the list at the top of the page to see all its specifications and options. Other measuring ranges are available on request.
Alarm and options by model
- E2638 : optional: 2 relays 5 A, LEDs and 85 dB buzzer or LCD display ; relays, buzzer and LEDs, built-in or remote LCD display (0 to +50 °C), self-test button, 3 m remote probe, 90-265 VAC.
- E2639 : 3 relays (pre-alarm, alarm, fault), 4 LEDs, 85 dB buzzer, 2 × 24 V beacon outputs ; WiFi with web server, replaceable pre-calibrated GSH sensor, 2.5 or 5 m remote probe (GSH version).
- E2608 : 2 SPST relays 5 A ; duct version, 3 m remote probe, 24 VAC or 230 VAC.
- E2618 : none: alarm handled by the PLC ; duct version, 3 m remote probe.
- E2648 : optional 2 SPST relays 5 A ; relays, 3 m remote probe, 24 VAC or 230 VAC.
- E2617 : none: alarm handled by the PLC ; none.
Request a quote
Afric Froid supplies and installs Evikon gas detectors with its refrigeration systems in Tunisia, Algeria, Senegal and Côte d’Ivoire. Tell us the room, its temperature, the number of points to monitor, the power supply and how the alarm should be given: we select the model and send you a quote.
See all our gas detectors and sensors.
| Model | E2638-O2 · multi-option IP65, E2639-O2 · 3 relays, buzzer, E2608-O2 · 2 relays, wall/duct, E2618-O2 · transmitter, no relays, E2648-O2 · aluminium IP66, E2617-O2 · low-cost transmitter |
|---|
Official Evikon documents, kept up to date by the manufacturer:
Related products
Ammonia (NH3) gas detector (R717)
Ethylene (C2H4) gas detector
Hydrogen (H2) gas detector
Carbon monoxide (CO) gas detector
Fixed carbon monoxide (CO) detectors for car parks, loading bays, warehouses with combustion-engine forklifts and boiler rooms: electrochemical cell from 0-100 to 0-1,000 ppm, lifetime over 10 years. Relay and buzzer alarms, or 4-20 mA transmitters for ventilation control. Choose the model below to see its specifications and options.