Danfoss EVR v2 solenoid valves (EVR 2 to EVR 40)
Complete range of Danfoss EVR v2 refrigeration solenoid valves for liquid, suction and hot gas lines: from the EVR 2 (Kv 0.16 m³/h) to the EVR 40 (Kv 24.2 m³/h), normally closed or open, solder, flare or flange, and the EVRC bi-flow valve. 82 codes. Choose your size in the table below.
Danfoss EVR v2 solenoid valves are the most widely used controlled shut-off valves in commercial and industrial refrigeration. They open or close a liquid, suction or hot gas line on command from the thermostat or controller. The range runs from the EVR 2 (Kv 0.16 m³/h, about 2 kW in the liquid line with R404A) to the EVR 40 (Kv 24.2 m³/h, about 250 kW), in normally closed or normally open versions, with solder, flare or flange connections, plus the EVRC bi-flow valve. Afric Froid offers the 82 codes of the Danfoss data sheet, on quote.
Choose the size
| Type | Operation | Connections | Kv (m³/h) | Liquid R404A (kW) | Function | Models |
|---|---|---|---|---|---|---|
| EVR 2 | direct operated | solder 1/4″, 6 mm ; flare 1/4″ | 0.16 | 2.04 | NC | 3 |
| EVR 3 | direct operated | solder 1/4″, 3/8″, 6 mm, 10 mm ; flare 1/4″, 3/8″ | 0.27 | 3.68 | NC | 6 |
| EVR 4 | servo (diaphragm) | solder 3/8″ | 0.7 | 9.26 | NC | 1 |
| EVR 6 | servo (diaphragm) | solder 3/8″, 1/2″, 5/8″, 10 mm, 12 mm ; flare 3/8″, 1/2″ | 1 | 12.12 | NC / NO | 12 |
| EVR 8 | servo (diaphragm) | solder 1/2″, 5/8″ | 1.15 | 14.44 | NC | 3 |
| EVR 10 | servo (diaphragm) | solder 3/8″, 1/2″, 5/8″, 12 mm, 16 mm ; flare 1/2″, 5/8″ | 2.2 | 25.47 | NC / NO | 11 |
| EVR 15 | servo (diaphragm) | solder 5/8″, 7/8″, 16 mm, 22 mm ; flare 5/8″ ; flange | 3.3 | 39.23 | NC / NO | 9 |
| EVR 18 | servo (diaphragm) | solder 7/8″ | 3.9 | 51.36 | NC | 1 |
| EVR 20 | servo (diaphragm) | solder 7/8″, 1 1/8″, 28 mm ; flange | 6 | 81.46 | NC / NO | 9 |
| EVR 22 | servo (diaphragm) | solder 1 1/8″, 1 3/8″ | 6 | 92.90 | NC / NO | 4 |
| EVR 25 | servo (piston) | solder 1 1/8″, 1 3/8″, 28 mm | 9.8 | 101.06 | NC | 6 |
| EVR 32 | servo (piston) | solder 1 3/8″, 1 5/8″, 2 1/8″, 35 mm, 42 mm | 16.7 | 172.66 | NC | 8 |
| EVR 40 | servo (piston) | solder 1 5/8″, 2 1/8″, 42 mm | 24.2 | 249.71 | NC | 6 |
| EVRC 6, 15, 20 | bi-flow | solder 3/8″, 5/8″, 7/8″, 10 mm, 16 mm, 22 mm | 0.9 to 3.6 | – | NC | 3 |
Kv of the solder version without manual stem. Danfoss rated liquid capacity: evaporating −10 °C, liquid at 25 °C, pressure drop 0.15 bar. Click a type to see its models, its capacities with R22, R134a, R410A, R32, R290 and R600a, and its specifications.
A solenoid valve for every line
- Liquid line: the solenoid valve shuts off the evaporator feed when the system stops, for example in pump-down, and prevents liquid from migrating to the compressor.
- Suction line: it isolates one evaporator in a multi-evaporator system. Suction capacities are lower: choose the size from that line of the table on each page.
- Hot gas line: it controls hot gas injection for defrost or capacity control.
Three operating principles
- EVR 2 and EVR 3, direct operated: the coil opens the seat directly, with no minimum differential pressure.
- EVR 4 to EVR 22, servo operated diaphragm valves: the coil opens a pilot orifice and the system pressure opens the diaphragm. At least 0.03 bar of pressure difference is needed.
- EVR 25, 32 and 40, servo operated piston valves, for high flows: at least 0.2 bar of pressure difference.
The NC (normally closed) version is the most common: the valve is closed when the coil is de-energized. The NO (normally open) version, servo operated, is available from EVR 6 to EVR 22. The EVRC lets liquid flow in the reverse direction, for heat pumps and reverse hot gas defrost.
What version 2 brings
- Working pressure raised to 45.2 bar, and 49 bar under the PED for EVR 2 to 22 solder valves without manual stem: suitable for R410A and R32.
- More than 40 approved refrigerants, including the flammable R290, R600a, R32, R454B and R1234yf for EVR 2 to 22 solder valves without manual stem, and R1234ze(E) in oil-free systems.
- Media from −40 to 105 °C, up to 130 °C during defrost.
- Extended copper ends on solder versions: brazing without dismantling the valve.
- Optional manual stem from EVR 6 upwards, to open the valve with the coil de-energized.
Coils
EVR valve bodies are sold without coil. They take the Danfoss clip-on coils, 230 V AC or DC; the standard coil is the BE230AS (018F6701). The maximum opening differential pressure (MOPD) depends on the coil: 38 bar with a 10 W AC coil for all NC EVR valves.
Afric Froid, your Danfoss supplier
Afric Froid supplies Danfoss solenoid valves, coils and valves, installs them and provides after-sales service in Tunisia, Algeria, Senegal and Ivory Coast. Tell us the refrigerant, the capacity and the line (liquid, suction or hot gas): we will choose the right valve and coil and send you a quote.
Official Danfoss documents for EVR v2 solenoid valves, always in their latest version:
- EVR 2 - EVR 40 data sheet (PDF, 2025 edition, 3.3 MB): operation, codes, capacities and dimensions, including EVRC and flammable refrigerants.
- Installation guides: EVR 2 to EVR 22, EVR 25 and EVR 32 and 40 (PDF).