Danfoss EVR 8 v2 solenoid valve
Danfoss EVR 8 refrigeration solenoid valve (EVR v2), servo operated (diaphragm), Kv 1.15 m³/h: about 14.4 kW in the liquid line with R404A. 3 models, normally closed. Valve body sold without coil. Choose your model below to see its specifications.
The Danfoss EVR 8 (version 2) is a servo operated (diaphragm) solenoid valve for the liquid, suction and hot gas lines of refrigeration and air conditioning systems. With a Kv of 1.15 m³/h, it handles about 14.4 kW in the liquid line with R404A and 21.3 kW with R22 or R407C, at Danfoss rated conditions. It is available normally closed (NC), solder 1/2″, 5/8″. The valve body is sold without coil.
The models
| Code | Type | Function | Connection | Manual | Kv (m³/h) | Weight |
|---|---|---|---|---|---|---|
| 032L7121 | EVR 8 | NC | 1/2″ solder | no | 1.15 | 0.19 kg |
| 032L7148 | EVR 8 | NC | 1/2″ solder | yes | 1.09 | 0.29 kg |
| 032L7122 | EVR 8 | NC | 5/8″ solder | no | 1.15 | 0.24 kg |
NC = normally closed (closed with coil de-energized), NO = normally open (open with coil de-energized). Valve bodies supplied without coil.
Rated capacity (kW)
| Line | R22/R407C | R134a | R404A/R507 | R410A | R32 | R290 | R600a |
|---|---|---|---|---|---|---|---|
| Liquid | 21.32 | 19.73 | 14.44 | 20.90 | 29.88 | 23.74 | 23.90 |
| Suction | 2.35 | 1.71 | 2.05 | 2.96 | 3.78 | 2.88 | 1.60 |
| Hot gas | 9.51 | 7.33 | 7.81 | 11.68 | 15.37 | 10.85 | 6.68 |
Danfoss values. Liquid and suction: evaporating −10 °C, liquid at 25 °C ahead of the valve, pressure drop 0.15 bar. Hot gas: condensing 40 °C, pressure drop 0.8 bar, hot gas at 65 °C, subcooling 4 K. For other conditions, we run the calculation with Danfoss Coolselector.
Specifications
- Operation: servo operated (diaphragm). Minimum opening differential pressure 0.03 bar.
- MOPD (maximum opening differential pressure, liquid line): 38 bar with a 10 W AC coil, 28 bar with a 20 W DC coil.
- Pressures: 45.2 bar maximum working pressure (solder versions); 49 bar under the PED for solder versions without manual stem.
- Media temperature: −40 to 105 °C, and up to 130 °C during defrost.
- Refrigerants: more than 40 refrigerants approved by Danfoss, including R404A, R507A, R407C, R410A, R134a, R448A, R449A, R452A, R513A and R22. Solder versions without manual stem also accept the flammable refrigerants R290, R600a, R32, R454B, R454C, R455A and R1234yf; flare versions, A2L only. Details in each model.
- Construction: brass body, extended copper ends on solder versions, so the valve does not need to be dismantled for brazing.
- Manual operation (“+ manual” models): a stem opens the NC valve with the coil de-energized, in about 6 turns, for example for evacuation or troubleshooting. Close it again and refit the cap afterwards.
- Test magnet: any EVR NC or NO valve can also be opened or closed by hand, with the coil removed, using the Danfoss 018F0091 magnet.
Coil
The valve body is sold without coil. EVR valves take the Danfoss clip-on coils: the standard coil is the BE230AS (018F6701, 230 V AC, IP67 terminal box), as given in the Danfoss data sheet. The maximum opening differential pressure (MOPD) depends on the coil: the values given here are those of the Danfoss data sheet, with a 10 W AC or 20 W DC coil. For an ATEX zone, see the BV024A coil.
All sizes are listed in our Danfoss EVR v2 solenoid valve range, with a selection table. Neighbouring sizes: EVR 6 and EVR 10. For a reversible circuit, see the EVRC bi-flow solenoid valve.
Afric Froid, your Danfoss supplier
Afric Froid supplies Danfoss solenoid valves, coils and valves, installs them and provides after-sales service in Tunisia, Algeria, Senegal and Ivory Coast. Tell us the refrigerant, the capacity and the line (liquid, suction or hot gas): we will choose the right valve and coil and send you a quote.
| Model | 1/2″ solder · NC (032L7121), 1/2″ solder · NC + manual (032L7148), 5/8″ solder · NC (032L7122) |
|---|
Official Danfoss documents for EVR v2 solenoid valves, always in their latest version:
- EVR 2 - EVR 40 data sheet (PDF, 2025 edition, 3.3 MB): operation, codes, capacities and dimensions, including EVRC and flammable refrigerants.
- EVR 2 to EVR 22 installation guide (PDF, 0.7 MB): mounting, brazing and tightening torques.