AKV 10P electric expansion valve, brazed (P1 to P8)

Danfoss AKV 10P electric expansion valve, brazed (ODF), from AKV 10P1 to AKV 10P8, i.e. 0.64 to 18.1 kW with R404A: choose your model below.

Request a quote

SKU: N/A Category:
Description

The Danfoss AKV 10P electric expansion valve controls the refrigerant injection into the evaporator and is driven by an electronic controller. It has brazed (ODF) connections and comes in eight orifice sizes, from AKV 10P1 (0.64 kW with R404A) to AKV 10P8 (18.1 kW with R404A): the model is chosen according to the evaporator capacity. Select your model at the top of the page to see its reference and specifications.

AKV 10P models and their cooling capacity

Model Danfoss code Capacity R404A / R507 Capacity R407A Capacity CO2 (R744) Inlet × outlet Orifice kv value Max. MOPD
AKV 10P1 068F5211 0.64 kW 0.90 kW 1.17 kW 3/8″ × 1/2″ 0.50 mm 0.009 m³/h 70 bar
AKV 10P2 068F5212 1.12 kW 1.58 kW 2.06 kW 3/8″ × 1/2″ 0.65 mm 0.015 m³/h 70 bar
AKV 10P3 068F5213 1.72 kW 2.41 kW 3.14 kW 3/8″ × 1/2″ 0.80 mm 0.024 m³/h 55 bar
AKV 10P4 068F5214 3.33 kW 4.68 kW 6.10 kW 3/8″ × 1/2″ 1.10 mm 0.046 m³/h 55 bar
AKV 10P5 068F5215 4.64 kW 6.52 kW 8.49 kW 3/8″ × 1/2″ 1.30 mm 0.064 m³/h 55 bar
AKV 10P6 068F5216 8.27 kW 11.60 kW 15.14 kW 3/8″ × 1/2″ 1.70 mm 0.114 m³/h 42 bar
AKV 10P7 068F5217 13.40 kW 18.81 kW 24.58 kW 1/2″ × 5/8″ 2.30 mm 0.185 m³/h 20 bar
AKV 10P8 068F5218 18.10 kW 25.40 kW 33.26 kW 1/2″ × 5/8″ 3.00 mm 0.250 m³/h 20 bar

Danfoss rated capacities. R404A/R507 and R407A: evaporating at +4 °C, condensing at 38 °C, liquid at 37 °C. CO2 (R744): evaporating at −10 °C, condensing at 0 °C, 1 K subcooling. MOPD with Danfoss coil 018F6905 (230 V AC, 19 W); it is lower with other coils.

Common specifications

Type Electric expansion valve, normally closed (NC), angle-way
Connections Brazed (ODF), inlet and outlet
Coil Not included, to be ordered separately
Max. working pressure 90 bar
Media temperature −50 to +60 °C
Ambient temperature −50 to +50 °C
Weight without coil 0.30 kg (P1 to P6), 0.343 kg (P7 and P8)
Approvals C UL US, EAC
Refrigerants R407A, R407F, R422B, R422D, R448A, R449A, R449B, R450A, R452A, R513A, R1234yf, R1270, R290, R32, R407H, R438A, R444B, R452B, R454B, R454C, R455A, R463A, R513B, R515A, R515B, R516A, R600, R600a, R134a, R22, R23, R404A, R407C, R410A, R744, R1233zd(E), R1234ze(E), R507A, R454A, R469A
Additional information
ModelAKV 10P1 – 0.64 kW (R404A), AKV 10P2 – 1.12 kW (R404A), AKV 10P3 – 1.72 kW (R404A), AKV 10P4 – 3.33 kW (R404A), AKV 10P5 – 4.64 kW (R404A), AKV 10P6 – 8.27 kW (R404A), AKV 10P7 – 13.40 kW (R404A), AKV 10P8 – 18.10 kW (R404A)