AKV 20 electric expansion valve, brazed (AKV 20-1 to 20-5)
Danfoss AKV 20 electric expansion valve, brazed (ODF), from AKV 20-1 to AKV 20-5, i.e. 72 to 446 kW with R404A: choose your model below.
The Danfoss AKV 20 electric expansion valve controls the refrigerant injection into the evaporator and is driven by an electronic controller using pulse-width modulation. It has brazed (ODF) connections and comes in five orifice sizes, from AKV 20-1 (72 kW with R404A) to AKV 20-5 (446 kW with R404A). For lower capacities, see the AKV 15. Select your model at the top of the page to see its reference and specifications.
AKV 20 models and their cooling capacity
| Model | Danfoss code | Capacity R404A / R507 | Capacity R134a | Capacity R407A | Capacity CO2 (R744) | Inlet × outlet | kv value |
|---|---|---|---|---|---|---|---|
| AKV 20-1 | 042H2020 | 72 kW | 79.5 kW | 102 kW | 131 kW | 1 3/8″ × 1 3/8″ | 1 m³/h |
| AKV 20-2 | 042H2022 | 115 kW | 127 kW | 162 kW | 210 kW | 1 3/8″ × 1 3/8″ | 1.6 m³/h |
| AKV 20-3 | 042H2024 | 180 kW | 197 kW | 252 kW | 328 kW | 1 5/8″ × 1 5/8″ | 2.5 m³/h |
| AKV 20-4 | 042H2027 | 286 kW | 311 kW | 400 kW | 526 kW | 2 1/8″ × 2 1/8″ | 4 m³/h |
| AKV 20-5 | 042H2029 | 446 kW | 478 kW | 620 kW | 835 kW | 2 1/8″ × 2 1/8″ | 6.3 m³/h |
Danfoss rated capacities at +4.4 °C evaporating, 38 °C condensing and 37 °C liquid temperature. AKV 20 is not suitable for CO2 (R744) when the media temperature stays below 0 °C.
Common specifications
| Type | Servo-operated electric expansion valve, normally closed (NC) |
| Connections | Brazed (ODF), inlet and outlet; weld versions on request |
| Coil | Not included, to be ordered separately |
| MOPD | 18 bar |
| Max. working pressure | 28 bar |
| Evaporating temperature | −40 to +60 °C |
| Ambient temperature | −40 to +50 °C (depending on the coil) |
| Control | Pulse-width modulation (6 s period), 10 to 100 % of capacity |
| Filter | External 100 µm filter required upstream |
| Refrigerants | R134a, R22, R23, R404A, R407A, R407C, R407F, R407H, R410A, R422B, R422D, R438A, R448A, R449A, R449B, R450A, R452A, R463A, R507, R513A, R513B, R515A, R515B, R744 |
| Model | AKV 20-1 – 72 kW (R404A), AKV 20-2 – 115 kW (R404A), AKV 20-3 – 180 kW (R404A), AKV 20-4 – 286 kW (R404A), AKV 20-5 – 446 kW (R404A) |
|---|
Official Danfoss documents, always in their latest version:
- AKV 15 / AKV 20 data sheet (PDF, 1.3 MB): capacities per refrigerant, connections, coils and dimensions.
- AKV 20 installation guide (multilingual PDF, 0.6 MB): mounting, filter, brazing and commissioning.