1,927 m³ Frozen Cold Room – Bissau
1,927 m³ Frozen Cold Room – Bissau
A 9 m high room at −20 °C for 480 tonnes of frozen meat
Fourth phase of a meat importer’s cold store in Bissau: a new frozen room at −20 °C, 19.86 × 10.78 m and 9 m high, next to the 2025 rooms. It stores about 480 tonnes of frozen meat.
With this extension, the site has 8 frozen rooms, more than 10,000 m³ and about 2,500 tonnes of storage, all built by Afric Froid since 2023.
Address
Bissau, Guinea-Bissau
Scope of work
Technical study, insulation, supply, installation and commissioning.
Sector
Meat – Frozen meat storage
Duration
2026
The solution delivered
Background and client needs
The client wanted to increase capacity again, on the model of the 2025 rooms: 9 m high and up to 48 tonnes of meat to bring in every day.
Our work
AFRIC FROID carried out the heat-load calculation (54 kW) and the layout, then supplied and installed the insulation, the refrigeration equipment and the electrical work.
The room is cooled by two 29.2 kW Thermokey cubic evaporators (197 m² of exchange surface, 630 mm fans), each fed by its own 27 kW Bock HGX66e housed condensing unit. These latest-generation compressors have mexFLOW valve plates, which improve efficiency.
Danfoss electronic expansion valves and a Danfoss AK-CC55 controller with a Bluetooth display: the calculation gives about 30% less energy use than with thermostatic expansion valves.
Insulation is 150 mm polyurethane panels, with a 2 × 2.6 m sliding freezer door. Installation was carried out by an assembly and brazing team and a wiring team, each with a Tunisian Afric Froid technician.
Earlier phases on the site: the first two rooms in 2023, the 2024 extension and the 9 m high rooms of 2025.
See also our cold rooms, our page on refrigeration for meat and the frozen storage cold rooms in Abidjan.
Project highlights
Add about 480 tonnes of storage at −20 °C, on the same model as the 9 m rooms of 2025.
A 1,927 m³ room with two Bock HGX66e units, two Thermokey evaporators, electronic expansion valves and Danfoss AK-CC55 controls.
A stable −20 °C, a room that stays cold if a unit stops, and about 30% less energy use.