Danfoss KP 1 low pressure switch
Danfoss KP 1 low pressure switch for the protection and control of refrigeration compressors: range −0.9 to 7.5 bar, 1/4″ flare connection, 16 A changeover contact. Two versions, with automatic or manual reset. Choose your model below to see its specifications.
The Danfoss KP 1 is a low pressure switch for refrigeration and air conditioning systems. It protects the compressor against excessively low suction pressure and can also start and stop it, for example in pump-down operation. Its bounce-free snap-action contact keeps an accurate cut-out point and resists vibration.
The two versions
| Code | Reset | Setting range | Differential | Enclosure | Weight |
|---|---|---|---|---|---|
| 060-110166 | automatic | −0.2 to 7.5 bar | 0.7 to 4 bar, adjustable | IP44 | 0.3 kg |
| 060-110366 | manual (min.) | −0.9 to 7 bar | 0.7 bar, fixed | IP30 (IP44 with top cover 060-109766) | 0.29 kg |
Gauge pressures. 1/4″ (6 mm) male flare connection, DIN 8906. The automatic version comes with its top cover (IP44). On request: solder versions 1/4″ ODF (060-111266 automatic, 060-111166 manual) and 6 mm ODF (060-111066 automatic, 060-110966 manual).
Common specifications
- Contact: snap-action single-pole double-throw (SPDT), AC1 16 A, AC3 16 A and AC15 10 A at 400 V; DC13 12 W at 220 V. It can switch a single-phase motor of up to about 2 kW directly.
- Pressures: maximum working pressure 17 bar, test pressure 20 bar.
- Temperatures: ambient −25 to 65 °C (80 °C for 2 h max.); media −50 to 100 °C.
- Refrigerants: R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A and R513A, as well as the A2L refrigerants R454C, R455A, R1234yf and R1234ze with the precautions set out by Danfoss.
- Wiring: cable entry for 6 to 14 mm cable (Pg 13.5 possible), 0.75 to 2.5 mm² wires.
- Tool-free test: a manual trip lever lets you operate the contact by hand to check the wiring.
- Approvals: PED 2014/68/EU category IV (EN 12263) and UL.
Setting
Automatic version: set the cut-in pressure on the “CUT-IN” scale (one turn ≈ 0.7 bar), then the differential on the “DIFF” scale (one turn ≈ 0.15 bar). The cut-out pressure equals the cut-in pressure minus the differential; it must stay above absolute vacuum (−1 bar). Manual version: set the cut-out pressure; the reset button works once the pressure has risen by 0.7 bar. Always check the switching points with an accurate pressure gauge.
See also our Danfoss pressure switches KP 5 (high pressure), KP 15 (dual LP/HP) and MP 55 (oil differential).
Afric Froid, your Danfoss supplier
Afric Froid supplies Danfoss pressure switches and thermostats, installs them and provides after-sales service in Tunisia, Algeria, Senegal and Ivory Coast. Tell us the refrigerant and pressures of your system: we will choose the right model and send you a quote.
| Model | KP 1 automatic reset (060-110166), KP 1 manual reset (060-110366) |
|---|
Official Danfoss documents for KP pressure switches, always in their latest version:
- KP pressure switch data sheet (PDF, 2022 edition, 1.7 MB): specifications, setting, dimensions and codes, including A2L refrigerants.
- KP 1 to KP 7 installation guide (PDF, 0.7 MB): mounting, wiring and setting.
Related products
Danfoss KP 15 dual pressure switch (LP/HP)
Danfoss KP 5 high pressure switch
Danfoss MP 55 oil differential pressure switch
Danfoss MP 55 oil differential pressure switch: it stops the compressor when the lubricating oil pressure is too low. Adjustable differential 0.3 to 4.5 bar, 1/4″ flare connections. Five versions, with 45, 60, 90 or 120 s release time, or without time relay. Choose your model below to see its specifications.