Danfoss KP 15 dual pressure switch (LP/HP)
Danfoss KP 15 dual low and high pressure switch for the protection of refrigeration compressors: LP −0.9 to 7.5 bar, HP 8 to 32 bar, 1/4″ flare connections, 16 A changeover contact. Four versions, with automatic, manual or convertible reset. Choose your model below to see its specifications.
The Danfoss KP 15 combines a low pressure switch and a high pressure switch in one housing. It protects the compressor against both excessively low suction pressure and excessively high discharge pressure, with a single unit to wire. Its changeover contact controls the compressor, and a signal contact indicates a low pressure fault.
The four versions
| Code | Reset | LP range | LP differential | Enclosure | Weight |
|---|---|---|---|---|---|
| 060-124166 | LP auto, HP auto | −0.2 to 7.5 bar | 0.7 to 4 bar, adjustable | IP44 | 0.47 kg |
| 060-124366 | LP auto, HP manual | −0.2 to 7.5 bar | 0.7 to 4 bar, adjustable | IP30 (IP44 with top cover 060-109866) | 0.43 kg |
| 060-124566 | LP manual, HP manual | −0.9 to 7 bar | 0.7 bar, fixed | IP30 (IP44 with top cover 060-109866) | 0.44 kg |
| 060-126166 | convertible (LP and HP) | −0.9 to 7 bar | 0.7 bar, fixed | IP30 (IP44 with top cover 060-109866) | 0.43 kg |
HP side, all versions: range 8 to 32 bar, fixed 4 bar differential. Gauge pressures. 1/4″ (6 mm) male flare connections, DIN 8906. Only the automatic version comes with its top cover (IP44). On request: 060-124166 with 1/4″ ODF solder connections (060-125466), versions with separate LP and HP signals (060-126566 automatic, 060-126466 HP manual).
Common specifications
- Contact: snap-action single-pole double-throw (SPDT), AC1 16 A, AC3 16 A and AC15 10 A at 400 V; DC13 12 W at 220 V. It can switch a single-phase motor of up to about 2 kW directly.
- Pressures: LP side, maximum working pressure 17 bar and test pressure 20 bar; HP side, 35 bar.
- Temperatures: ambient −40 to 65 °C (80 °C for 2 h max.); media −50 to 100 °C.
- Refrigerants: R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A and R513A, as well as the A2L refrigerants R454C, R455A, R1234yf and R1234ze with the precautions set out by Danfoss.
- Wiring: cable entry for 6 to 14 mm cable (Pg 13.5 possible), 0.75 to 2.5 mm² wires.
- Tool-free test: a manual trip lever lets you operate the contact by hand to check the wiring.
- Good to know: the KP 15 is not intended for R410A or CO2 (R744). It is not PED-approved as a safety device (EN 12263): the certified version is the KP 17, with double bellows on the HP side.
- Weight: about 0.5 kg.
Setting
LP side (automatic reset): set the cut-in pressure on the “CUT-IN” scale (one turn ≈ 0.7 bar) and the differential on “DIFF” (one turn ≈ 0.15 bar). HP side: set the cut-out pressure on “CUT-OUT” (one turn ≈ 2.3 bar); the compressor restarts, or manual reset becomes possible, once the pressure has fallen by 4 bar. Always check the switching points with an accurate pressure gauge.
See also our Danfoss pressure switches KP 1 (low pressure), KP 5 (high pressure) and MP 55 (oil differential).
Afric Froid, your Danfoss supplier
Afric Froid supplies Danfoss pressure switches and thermostats, installs them and provides after-sales service in Tunisia, Algeria, Senegal and Ivory Coast. Tell us the refrigerant and pressures of your system: we will choose the right model and send you a quote.
| Model | KP 15 LP auto / HP auto (060-124166), KP 15 LP auto / HP manual (060-124366), KP 15 LP manual / HP manual (060-124566), KP 15 convertible reset (060-126166) |
|---|
Official Danfoss documents for KP pressure switches, always in their latest version:
- KP pressure switch data sheet (PDF, 2022 edition, 1.7 MB): specifications, setting, dimensions and codes, including A2L refrigerants.
- KP 15 and KP 17 installation guide (PDF, 0.7 MB): mounting, wiring and setting.
Related products
Danfoss KP 1 low pressure switch
Danfoss KP 5 high pressure switch
Danfoss MP 55 oil differential pressure switch
Danfoss MP 55 oil differential pressure switch: it stops the compressor when the lubricating oil pressure is too low. Adjustable differential 0.3 to 4.5 bar, 1/4″ flare connections. Five versions, with 45, 60, 90 or 120 s release time, or without time relay. Choose your model below to see its specifications.