AKV 10PS servo-operated electric expansion valve, brazed (PS4 to PS8)

Danfoss AKV 10PS servo-operated electric expansion valve, brazed (ODF), from AKV 10PS4 to AKV 10PS8, i.e. 3.33 to 18.1 kW with R404A: choose your model below.

Request a quote

SKU: N/A Category:
Description

The Danfoss AKV 10PS electric expansion valve controls the refrigerant injection into the evaporator and is driven by an electronic controller. It is the servo-operated version of the AKV 10P: it dampens pressure surges better and reaches a high MOPD with a low-power coil. It has brazed (ODF) connections and comes in five sizes, from AKV 10PS4 (3.33 kW with R404A) to AKV 10PS8 (18.1 kW with R404A). Select your model at the top of the page to see its reference and specifications.

AKV 10PS models and their cooling capacity

Model Danfoss code Capacity R404A / R507 Capacity R407A Capacity CO2 (R744) Inlet × outlet kv value
AKV 10PS4 068F4044 3.33 kW 4.68 kW 6.10 kW 3/8″ × 1/2″ 0.046 m³/h
AKV 10PS5 068F4045 4.64 kW 6.52 kW 8.49 kW 3/8″ × 1/2″ 0.064 m³/h
AKV 10PS6 068F4046 8.27 kW 11.60 kW 15.14 kW 3/8″ × 1/2″ 0.114 m³/h
AKV 10PS7 068F4047 13.40 kW 18.81 kW 24.58 kW 1/2″ × 5/8″ 0.204 m³/h
AKV 10PS8 068F4048 18.10 kW 25.40 kW 33.26 kW 1/2″ × 5/8″ 0.250 m³/h

Danfoss rated capacities. R404A/R507 and R407A: evaporating at +4 °C, condensing at 38 °C, liquid at 37 °C. CO2 (R744): evaporating at −10 °C, condensing at 0 °C, 1 K subcooling.

Common specifications

Type Servo-operated electric expansion valve, normally closed (NC), angle-way
Connections Brazed (ODF), inlet and outlet
Coil Not included, to be ordered separately
Max. working pressure 90 bar
MOPD 55 bar with Danfoss coil 018F6905 (230 V AC, 19 W); lower with other coils
Media temperature −50 to +60 °C
Ambient temperature −50 to +50 °C
Filter A filter finer than 40 µm is required upstream (Danfoss DML or DMSC filter drier recommended)
Refrigerants R407A, R407F, R422B, R422D, R448A, R449A, R449B, R450A, R452A, R513A, R1234yf, R1270, R290, R32, R407H, R438A, R444B, R452B, R454B, R454C, R455A, R463A, R513B, R515A, R515B, R516A, R600, R600a, R134a, R22, R23, R404A, R407C, R410A, R744, R1233zd(E), R1234ze(E), R507A, R454A, R469A
Additional information
ModelAKV 10PS4 – 3.33 kW (R404A), AKV 10PS5 – 4.64 kW (R404A), AKV 10PS6 – 8.27 kW (R404A), AKV 10PS7 – 13.40 kW (R404A), AKV 10PS8 – 18.10 kW (R404A)
Documentation

Official Danfoss documents, always in their latest version: